An Electrical Installation Condition Report (EICR) is a formal inspection and test of a property’s fixed electrical installation — the wiring, consumer unit, socket outlets, light fittings and permanently connected equipment — carried out by a qualified and competent electrician. Its purpose is to confirm whether the installation is safe for continued use, and to identify any damage, deterioration, defects, or non-compliance with the current UK wiring standard, BS 7671. Every issue found during the inspection is given a classification code — C1, C2, C3 or FI — so property owners, landlords and tenants can immediately see how serious it is. In England, an EICR is a legal requirement for private rented properties. It is also strongly recommended for owner-occupied homes and is a standard part of maintaining a safe commercial premises.

What Does EICR Stand For?
EICR stands for Electrical Installation Condition Report. It is sometimes referred to by its older name, Fixed Wire Testing — the two terms describe the same underlying process, with the EICR report as the end result.
What Is an EICR?
An EICR is a documented assessment of an existing electrical installation’s condition, produced after a qualified electrician has visually inspected and electrically tested the fixed wiring and associated components. Unlike a certificate issued for brand-new work, an EICR looks at an installation that is already in use — checking it against the current edition of the wiring regulations rather than the regulations in force when it was originally installed. This is why it is also known as Fixed Wire Testing. The result is a formal written report, not a pass/fail slip: it records every observation made, assigns a code to anything that falls short of a safe standard, and gives an overall verdict of either Satisfactory or Unsatisfactory.
What Is the Purpose of an EICR?
An EICR exists to protect people and property from the two main risks a deteriorating electrical installation creates: electric shock and electrical fire. Specifically, it is used to:
- Confirm whether an installation remains safe for continued use
- Identify damage, wear, corrosion or deterioration that has developed since the installation was last inspected
- Identify defects that could cause danger, such as inadequate earthing or bonding, or the absence of RCD (residual current device) protection
- Highlight any work that does not meet the current edition of BS 7671, even if it was compliant when originally installed
- Provide documented evidence of compliance for landlords, insurers, mortgage lenders, local authorities and, where relevant, employers
What Does an EICR Test Involve?
An EICR combines a visual inspection with a series of electrical tests, carried out in a set sequence:
1. Visual inspection
The electrician examines the consumer unit, visible cabling, sockets, switches and light fittings for damage, overheating, incorrect components, or non-compliant previous work, and checks whether adequate RCD protection is in place. An outdated or overloaded consumer unit is one of the most common causes of an Unsatisfactory result, and upgrading it is often the fastest way to resolve one.
2. Dead testing
With the relevant circuit isolated, the electrician tests continuity of protective conductors, insulation resistance, and polarity, to confirm the wiring itself is sound and correctly connected.
3. Live testing
With the circuit re-energised, the electrician measures earth fault loop impedance and tests the operation of any RCDs, to confirm the installation will disconnect safely in the event of a fault.
4. Reporting and coding
Every observation is recorded against the relevant circuit, given a classification code (see below), and the report concludes with an overall Satisfactory or Unsatisfactory result, plus a recommended date for the next inspection.
How Long Does an EICR Take?
Duration depends mainly on the number of circuits, the age and accessibility of the installation, and whether the property is domestic or commercial:
Property type | Typical duration |
|---|---|
Studio / one-bedroom flat | 1 – 2 hours |
Two to three-bedroom house | 2 – 4 hours |
Four-bedroom-plus / larger property | 4 – 6 hours |
Small commercial premises | Half a day |
Larger commercial / industrial premises | Full day or more, depending on scale |
Power is isolated only in short bursts while individual circuits are dead-tested, not for the full duration of the visit. Older installations, restricted access to sockets or the consumer unit, and any faults found along the way will all extend the appointment.
Who Is Responsible for Arranging an EICR?
- Landlords — under the Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020, landlords are legally responsible for arranging a landlord electrical safety certificate inspection at least every 5 years, providing a copy to tenants, and completing any C1, C2 or FI remedial work within the required timeframe.
- Homeowners — there is no legal duty, but a residential EICR roughly every 10 years is the standard safety recommendation for an owner-occupied property, and mortgage lenders and conveyancing solicitors frequently ask for a recent report during a sale.
- Employers and commercial premises owners — the Electricity at Work Regulations 1989 place a general duty to maintain electrical systems in a safe condition. A satisfactory commercial EICR is the standard way of demonstrating that duty has been met, typically every 5 years, or every 3 years for higher-risk premises such as industrial units.
- Managing agents and freeholders — typically responsible for arranging EICRs covering the communal electrical installation in blocks of flats.
Is an EICR a Legal Requirement?
Yes, for private landlords in England. Under the Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020, an EICR became mandatory for new tenancies from 1 July 2020 and for all existing tenancies from 1 April 2021. Landlords must have the installation inspected and tested at intervals of no more than 5 years, give existing tenants a copy within 28 days and new tenants a copy before they move in, and provide a copy to the local authority within 7 days if requested. Any C1, C2 or FI finding must be remedied. Failure to comply can result in a civil penalty of up to £40,000 per breach (correct as of 1 May 2026), and an invalid or missing EICR can also prevent a landlord from successfully pursuing a Section 8 possession claim.
Scotland, Wales and Northern Ireland have their own equivalent electrical safety obligations for rented property, with some differences in scope and enforcement, so landlords letting outside England should check the specific rules that apply in that nation. For owner-occupied homes, an EICR is not a legal requirement, but it is widely recommended as good practice.
How Long Do EICR Certificates Last?
An EICR does not expire in the way a certificate with a fixed cut-off date does — it is a record of the installation’s condition at the time of inspection, together with a recommended date for the next check. In practice, that recommended interval is treated as the certificate’s validity period:
Property type | Typical recommended interval |
|---|---|
Rented residential property | Maximum 5 years (legal requirement in England) |
Owner-occupied home | Recommended every 10 years |
Commercial premises | Typically every 5 years, or every 3 years for higher-risk premises |
Older installations / properties with identified issues | A shorter interval, sometimes 1 – 2 years, may be recommended in the report itself |
Where the report recommends a shorter interval than the standard maximum, that shorter date takes precedence.
Codes of EICR: Understanding EICR Classification Codes
Every observation on an EICR is assigned one of four codes, which determine whether the overall report is Satisfactory or Unsatisfactory:
Code | Meaning | What it means in practice |
|---|---|---|
C1 | Danger present | A risk of injury exists right now. This is usually made safe on the spot, before the electrician leaves, rather than left until a follow-up visit. |
C2 | Potentially dangerous | An urgent risk that needs remedial action, typically within 28 days for rented property. |
C3 | Improvement recommended | Not dangerous, and does not on its own make the report Unsatisfactory — closer to an MOT advisory than a fail. |
FI | Further investigation | A suspected but unconfirmed issue that could not be fully assessed during the visit and must be investigated without delay. |
A report with any C1, C2 or FI code is marked Unsatisfactory, and that remedial work must be carried out and, for rented property, confirmed in writing within the legal timeframe. If an FI code is raised, tracing the underlying issue is usually handled through electrical fault finding before the report can be finalised as satisfactory. A report with C3 observations only — or no observations at all — is marked Satisfactory.
Difference Between EIC and EICR
An EIC and an EICR are frequently confused, but they cover different situations and are not interchangeable:
EIC (Electrical Installation Certificate) | EICR (Electrical Installation Condition Report) |
|---|---|
Issued once, when new electrical work or a notifiable alteration is completed | Issued repeatedly, at intervals, to check an existing installation |
Certifies that new work complies with BS 7671 at the point it was finished | Reports on the current safety and condition of an installation already in use |
Does not reflect how the installation is ageing afterwards | Specifically designed to catch deterioration, damage and wear over time |
Only covers the work actually carried out — a kitchen rewire, a new circuit, a consumer unit change | Covers the whole fixed installation being assessed |
A recent full-installation EIC — less than 5 years old and covering the entire property, such as a full rewire or new build — can sometimes satisfy a landlord’s legal obligation in place of an EICR. An EIC that only covers part of the installation does not remove the need for an EICR on the rest of the property. If there is any doubt, a full EICR is the safer option.
Purpose of an EICR: The Bigger Picture
Beyond the individual test results, the wider purpose of an EICR is risk management over the life of a property. Electrical installations degrade gradually — insulation ages, connections loosen, consumer units fall behind current safety standards — often without any visible warning sign before a fault causes a shock or a fire. A periodic EICR catches that deterioration on a predictable schedule, rather than relying on a visible fault to prompt action. For landlords this converts an open-ended safety risk into a documented, time-bound compliance process; for homeowners and businesses it provides independent, dated evidence that the property’s electrics were professionally assessed and found safe.
How Much Does an EICR Cost?
Pricing is based on property size for domestic inspections, and circuit count for commercial premises:
Domestic EICR
Property size | Price |
|---|---|
Studio | £77 |
1–3 Bedroom | £92 |
4 Bedroom | £102 |
5 Bedroom | £112 |
6+ Bedroom | £122 |
Commercial EICR
Circuit count | Price |
|---|---|
Up to 12 circuits | £188 |
12–36 circuits | £243 |
Prices shown are as currently published on liviosiv.co and exclude any remedial work identified during inspection. Larger commercial premises are quoted individually based on circuit count and number of distribution boards.
Services Often Booked Alongside an EICR
An EICR covers the fixed electrical installation only. It’s commonly booked together with:
- Portable Appliance Testing (PAT) — covers plug-in appliances such as kettles and portable heaters, which an EICR does not assess.
- Emergency Lighting Certificate — a separate requirement with its own renewal cycle, common in HMOs and commercial premises.
- Electrical repairs and installation — for wider fixes or upgrades beyond the specific remedial items flagged on an EICR.
Frequently Asked Questions
Do homeowners need an EICR?
There is no legal requirement for owner-occupied homes, but an EICR every 10 years is the standard safety recommendation, and buyers, conveyancers and mortgage lenders increasingly expect to see a recent report during a property sale.
What happens if a property fails an EICR (an Unsatisfactory report)?
Any C1, C2 or FI observations must be remedied. For rented property, landlords must complete the necessary work and provide written confirmation to the tenant and, if requested, the local authority, within 28 days or any shorter period stated in the report.
Is an EICR the same as a Gas Safety Certificate?
No. An EICR covers the fixed electrical installation. A Gas Safety Certificate (CP12) is a separate legal requirement covering gas appliances and pipework. Landlords typically need both.
Can a property be sold without an EICR?
An EICR is not a legal requirement for a sale in the way it is for a tenancy, but a current, satisfactory report reassures buyers and can support mortgage valuation and conveyancing, so many sellers arrange one proactively.